- Product description
-
Product descriptionCable tray with integrated quick fastening system. The usable length of the cable tray is 3,000 mm.
The cable tray has continuous side perforations of 7 x 20 mm for the installation of additional connection and mounting components.
From a cable tray width of 200 mm with 30% hole surface, suitable for use under sprinkler systems according to VdS guideline 2092.
- Technical data
-
Technical data
Colour zinc Connector version Integrated connector CO₂ Footprint (GWP) Cradle-to-Gate 8,048 kg CO₂e / 1 Meter Dimension 85x100x3050 Dimension B 100 mm Dimension L 30 mm Dimension y 62 mm Height 85 mm Length 3050 mm Load test type according to IEC 61537 Type II Magnetic shield insulation with cover 50 dB Magnetic shield insulation without cover 20 dB Maintain electrical functions no Material Steel Mounting perforation in base yes NATO hole pattern no NEMA load class 8C Plate thickness 1,5 mm Rustproof steel, pickled no Side perforation yes Support spacing 1.5 m 3,4 kN/m Support spacing 2.0 m 2,7 kN/m Support spacing 2.5 m 2,07 kN/m Support spacing 3.0 m 1,5 kN/m Surface Strip galvanized Type of connector, cable support system Click fastening Usable cross-section 8300 mm² Usable cross-section 83 cm² Wide-span version no Width 100 mm With cover no Technical data
Load diagram, cable tray, type SKSM 85
- Permitted cable tray/ladder load in kN/m without man load
- Support width in m
- Rail bend in mm at permitted kN/m
- Load scheme during testing
- Load curve with cable tray/ladder width in mm
- Strut bend curve according to support width
- All types
-
All types
- Downloads
-
Data sheet SKSM 810 FS / 6059530 , 0.40MB , pdfEU declaration of conformity SKSM 810 FS / 6059530 , 0.10MB , pdfUK Declaration of Conformity SKSM 810 FS / 6059530 , 0.09MB , pdfLabel approval VDE symbol approval KTS Magic , 0.18MB , pdfEnvironmental declaration Umweltproduktdeklaration (EPD) , 1.48MB , pdfMounting instructions Brief system instructions for MKSM, SKSM, RKSM , 0.04MB , pdfMounting instructions Rastbare Kabelrinnensysteme Magic , 11.60MB , pdfMounting instructions General information on the mounting , 2.61MB , pdf