- Product description
-
Product description• Spark gap to VDE 0185-561-3 (IEC 62561-3)
• Ex certificate to ATEX
• Labelling to EN 60079-0/-1: II 2 G Ex db IIC T6 Gb
• Labelling to EN 60079-0/-31: II 2 D Ex td IIIC T80 °C Db IP67
• Ex certificate to IECEx
• Labelling to EN 60079-0/-1: Ex db IIC T6 Gb
• Labelling to EN 60079-0/-31: Ex td IIIC T80 °C Db IP67
• Ex certificate to INMETRO
• Labelling to ABNT NBR IEC 60079-0/-1: Ex db IIC T6 Gb
• Labelling to ABNT NBR IEC 60079-31: Ex td IIIC T80 °C Db IP67
• Connection cable (25 mm2) on both sides, pre-mounted with M10 bolt, lock washer and nut
Application: In potentially explosive areas zone 1/21 and 2/22, indirect bridging of insulating flanges and insulating glands, e.g. in cathodic, corrosion-protected (KKS) systems.
- Technical data
-
Technical data
Colour Black Connecting cable length 0,35 m Connection Metric CO₂ Footprint (GWP) Cradle-to-Gate 1,517 kg CO₂e / 1 Piece Dimension 2x1m Explosion-tested version yes Ignition protection type Pressure-resistant encapsulation Lightning current carrying capacity H/100 kA Lightning impulse current 100 kA Material Hotmelt Material of the connection Die-cast zinc Nominal discharge surge current 100 kA Permitted temperature range, max. 60 °C Permitted temperature range, min. -20 °C Power frequency spark-over voltage 0,56 kV Protection rating IP65/67 Rated DC withstand voltage 354 V Rated impulse sparkover voltage 1,25 kV Rated power frequency withstand voltage 250 V - All types
- Downloads
-
Data sheet EX ISG H 350 2L / 5240033 , 0.17MB , pdfCatalogue Überspannungsschutz , 28.42MB , pdfEU declaration of conformity EX ISG H 350 2L / 5240033 , 0.66MB , pdfDeclaration of performance EX ISG H 350 2L / 5240033 , 0.34MB , pdfTest certificate BET testing certificate EX ISG H , 0.05MB , pdfLabel approval EU construction sample test certificate , 0.48MB , pdfLabel approval IECEx Certificate of Conformity , 0.05MB , pdfLabel approval DNV GL - Business Assurance , 0.15MB , pdfMounting instructions Mounting instructions EX ISG H spark gap , 0.15MB , pdfTechnical information Sample form for testing Ex spark gaps EX ISG H DE , 0.04MB , pdf
Eesti Vabariik - Eesti Keel