PV system solution, type 2, for inverter with 1 MPP tracker, 1,000 V DC

Item no. 5088657 | EAN 4012196775583

5088657 / PVG-C1000K 400
IP66
Product description

Product description

System solution for photovoltaic inverter with 1 separate MPP tracker

• Varistor arrester, connectable with cut-off unit in error-resistant Y circuit to VDE 0100-712 (50539-12)
• Low DC protection level: < 4.0 kV (Voc max = 1,000 V DC with V20-B+C/0-500PV)
• Per protection device, there are 8 terminals up to 6 mm² pre-mounted in the housing, up to 30 A DC per terminal
• Pre-mounted in polycarbonate housing (IP65), UV-resistant for use outside, including cable gland kit



For DC protection of the inverter in photovoltaic systems.

If there is a danger of condensation forming through wind, ice, temperature or sunlight, further measures may be necessary!


  • 5-year warranty
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • Protection device to DIN EN 61643-11 or IEC 61643-11
  • Transition from LPZ 1 to LPZ 2
  • Installation electrotechnical expertise
Technical data

Connectivity options

Anschlussart Generatoranschlusskasten Tension spring terminal
Cable type for surge protection devices Power cable DC (PV)
Conductor cross-section, flexible (fine-wire), min. 6 mm²
Conductor cross-section, rigid (single-wire/multiwire), max. 10 mm²
Conductor cross-section, rigid (single-wire/multiwire), min. 0,5 mm²
DC network form yes
Dimension 1000V DC
Entries per MPPT 4
Exits per MPPT 4
Housing material surge protection components PC
Installation type Pre-mounted in the housing
IT network form no
Lightning protection zone LPZ 1→2
Max. mains-side overcurrent protection 125
Max. PV voltage 1000 V
Maximum back-up fuse 125 A
Maximum continuous voltage DC 1000 V
Maximum discharge current (8/20 μs) 40 kA
Network form DC
Nominal discharge current (8/20 µs) 20 kA
Number of MPPTs 1
Operating temperature, max. 80 °C
Operating temperature, min. -40 °C
Other network form no
Pole version 3
Protection rating IP66
Remote signalling no
Response time <25 ns
Short-circuit resistant yes
Signalling on device Visual
SPD to EN 61643-11 Type 2
SPD to IEC 61643-1 Class II
Test class, type 2 yes
TN network form no
TN-C network form no
TN-C-S network form no
TN-S network form no
TT network form no
Version for Type 2 in housing with terminals
All types

All types

Types Protection rating Item no. Quantity SSU
PVG-C1000K 400 IP66 5088657